leak-detector-with-sensors-600x600

Ideal for Server Rooms or Basements, the Deeter Leak Detector System comprises a Leak Detector Controller and a series of Leak Detector Sensors connected in a chain to the Controller via a 3-core cable. The Sensors will detect a conductive liquid (e.g. water leak) between a pair of probes on their underside. The Controller will respond to a leak detected at any one of the Sensors.

The Controller provides an LED indication of wet or dry conditions and will also detect a fault, should one occur, in the sensor cable. The Controller provides three outputs (two SPDT relays and an open-collector transistor) that may be used to directly drive pumps and alarms, or may be used to interface to other equipment, such as Programmable Logic Controllers, Building Management Systems, and dial-up alarms systems.

Technical Data

Power to the Controller can be from a mains supply (220-240VAC) or a lowvoltage supply (10-24V), either AC or DC. Power to the Sensors is provided by the 3-core linking cable.

The Controller is housed in a UL94-V0 flame retardant case that will fit on a 35mm DIN rail. All inputs and outputs are via screw terminals.

Sensors come in an IP65 ABS enclosure and are simple to connect using cable lengths to suit the installation. Screw terminals are provided for the three wires in and the three wires out to the next Sensor in the chain.

The Sensor enclosure is held off the floor by rubber feet with two M3 threaded probes extending downwards to within 1mm of the floor. The probes may be extended using the threads if required. The enclosure also has provision for bolting the Sensors to the floor.

Behind the Controller front panel is a bank of DIP switches that allow a number of user-selectable options. The switches are visible through the front panel but are only accessible with the panel removed, so cannot accidentally be changed. Options include: assigning outputs to either a leak or a fault condition; setting the relays to default to open or closed; selecting outputs to latch so that they remain in the ‘wet’ state after a leak has dried. A Reset button is provided for clearing latched outputs.

 

Controller Dimensions 90mm x 71mm x 58mm Sensor Dimensions 100mm (incl. cable glands) x 64mm x 40mm high
Controller Mounting 35mm DIN rail Sensor Probes Pair, stainless steel, M3 thread, 5mm long, 20mm spacing.
Mains Power Supply option 220-240VAC @ 20mA Low Voltage Supply options 10-32VDC @ 200mA
8-24VAC @ 200mA
Relay Contacts 6A @ 250VAC Open-Collector Transistor Output Internally limited to 50mA. Maximum pull-up voltage, 40VDC
Maximum Number of Sensors per Controller tbd (>10) Maximum Sensor Cable Length Typically 2000m, depending on wire resistance (tbc)

Download the Leak Detector System Datasheet

Download the Leak Detector System User Guide